Capacity Voltage MCA / MOP Conductor Breaker (HACR) Disconnect Min Conduit Equipment Ground Torque Rating
9,000 BTU (115V) → 115V 12A / 15A 14 AWG Copper 15A Single-Pole 30A Non-Fused 1/2" Liquid-Tight or EMT 14 AWG Copper 10.6–13.3 in-lbs
12,000 BTU (115V) → 115V 16A / 20A 12 AWG Copper 20A Single-Pole 30A Non-Fused 1/2" Liquid-Tight or EMT 12 AWG Copper 10.6–13.3 in-lbs
12,000 BTU (208/230V) → 230V 9A / 15A 14 AWG Copper 15A Double-Pole 30A Non-Fused 1/2" Liquid-Tight or EMT 14 AWG Copper 10.6–13.3 in-lbs
18,000 BTU (208/230V) → 230V 16A / 20A 12 AWG Copper 20A Double-Pole 30A Non-Fused 1/2" Liquid-Tight or EMT 12 AWG Copper 13.3–15.0 in-lbs
24,000 BTU (208/230V) → 230V 21A / 30A 10 AWG Copper 30A Double-Pole 30A Non-Fused 3/4" Liquid-Tight or EMT 10 AWG Copper 15.0–18.0 in-lbs
30,000 BTU (208/230V) → 230V 26A / 35A 10 AWG Copper 35A Double-Pole 60A Non-Fused 3/4" Liquid-Tight or EMT 10 AWG Copper 15.0–18.0 in-lbs
36,000 BTU (208/230V) → 230V 32A / 45A 8 AWG Copper 45A Double-Pole 60A Non-Fused 3/4" or 1" EMT 10 AWG Copper 18.0–20.0 in-lbs

Engineering Standards & Conductor Ampacity Rules

Ductless heat pumps cannot be sized with standard residential 15A/20A lighting circuit assumptions (NEC 240.4(D)). Conductor gauge and overcurrent protection must be calculated independently:

  • Conductor Gauge (Sized to MCA): Pursuant to NEC 440.6, branch supply wires are sized to the Minimum Circuit Ampacity rating at 60°C insulation column (NEC Table 310.16). Built-in solid-state thermal overloads safeguard the wire against running overcurrent.
  • Circuit Breaker (Sized to MOP): Pursuant to NEC 440.22, the breaker is sized up to the Maximum Overcurrent Protection rating to absorb locked-rotor inrush current during DC inverter startup without tripping.
  • Equipment Grounding Conductor (EGC): Sized under NEC Table 250.122 based on the upstream circuit breaker rating (14 AWG copper for 15A circuits, 12 AWG for 20A, 10 AWG for 30A to 60A circuits).
  • Terminal Screw Torque (NEC 110.14(D)): Electrical terminations must be tightened with a calibrated torque tool to manufacturer ratings to avoid arcing and circuit board failures.

Need a Voltage Drop Calculation for Runs Over 50 Feet?

Continuous line resistance increases past 50 ft. Use our interactive calculation engine to verify voltage drop limits:

Launch Interactive Calculator →